SST Automation Communication Gateway: Bridging the Gap Between Networks and Protocols
SST Automation communication gateway is a leading provider of high-performance communication gateways that seamlessly connect different networks and protocols, enabling seamless data exchange and enhanced communication in industrial automation and IoT applications.
Modbus/BACnet IP Gateway (GT200-BM-2RS)
SST Automation’s GT200-BM-2RS connects multiple Modbus slave devices to the BACnet IP network.
- Protocol conversion between BACnet and Modbus.
- Ethernet 10/100M self-adaptive.
- BACnet IP can realize some services such as: Who Is, I Am, Who Has, I Have, Read Property, Write Property, Read Property Multiple.
- Supports at most 500 BACnet BI, 300 BO, 300 BV, 500 AI, 300 AO, 300 AV, 500 MSI and 100 MSO.
- Each serial support at most 100 commands.
- The two serial ports are RS485 interface, half duplex, baud rate: 9600, 19200, 38400, 57600, 115200bps optional, check bit: none, odd, even, mark and space optional, 1 or 2 bit stop bit optional.
- 1KV galvanic isolated on one RS485 interface.
- Power supply: 24VDC (11V-30V), 90mA (24VDC).
- Operating Temp: -4°F to 140°F (-20 °C to 60 °C); Rel. Humidity: 5%-95% (non-condensing).
- Dimension (WHD): 1.6in4.9in4.3in (40mm125mm110mm).
Modbus/Modbus TCP Gateway (GT200-MT-2RS)
SST Automation’s GT200-MT-2RS can realize the interconnection between Modbus TCP and Modbus RTU/ASCII. Its serial ports support RS485 and RS232
- Operating mode:
- Modbus RTU/ASCII slave mode: Modbus TCP masters communicate with Modbus RTU/ASCII slaves through the gateway.
- Modbus RTU/ASCII master mode: Modbus TCP slaves communicate with Modbus RTU/ASCII masters through the gateway.
- Slave modes:
- Support 4 Modbus TCP masters simultaneously communication and can support 32 simultaneous commands requests.
- Master modes:
- Support 4 different IPs or 4 Modbus TCP slaves of the different ports.
- Serial interface is RS485 and RS232, half-duplex, and baud rate support: 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 and 230400bps; check bit: none, odd, even, mark, space; 1 or 2 stop bits.
- Ethernet 10/100M self-adaptive.
- Two Ethernet RJ45 interfaces, built-in switch function, support cascade, can be used in a ring network, and can save cables and switches in field connections.
- Supports mapping slave ID.
- Supports automatically routing the requests to the serial interface.
- Supports network security settings: limit the communication client IP address range and set login password.
- Power supply: 24VDC (11V ~ 30V), 130mA (24VDC).
- Working temperature: -40°F to 185°F (-40°C to 85°C); Rel. Humidity: 5%- 95% (non-condensing).
- Dimensions (W*H*D): 0.98in*3.93in*3.54in (25mm *100mm *90mm).
- Installation: DIN Rail Mounting (35mm).
- Protection class: IP20.Mounting: DIN Rail Mounting (35mm)
Universal Serial/PROFIBUS DP Gateway (GT200-DP-RS)
SST Automation’s GT200-DP-RS connects serial devices to PROFIBUS DP network and establishes communication between them
- Acts as the PROFIBUS DP slave on PROFIBUS DP gateway side.
- RS232/422/485 Selection via software.
- Supports Modbus RTU/ASCII Master mode, Modbus RTU/ASCII Slave mode, and Generic Data mode.
- Serial: RS485, RS232, RS422, half-duplex.
- Serial Baud rate: 300, 600, 1200, 2400, 9600, 19.2 K, 38.4K, 57.6K and 115.2Kbps can be selected.
- As a PROFIBUS DP slave. Automatic baud rate detection on PROFIBUS DP (9600bit/s~12Mbit/s).
- Complete PROFIBUS DP V0 slave functionality according to EN50170 (IEC61158).
- Max Input: 244 bytes; Max Output: 244 bytes; Max Input+Output: 488 bytes.
- Power Supply: 11V-30VDC, Maximum Power Dissipation: 2W.
- Operating Temp.:-40°F to 158°F (-40°C to 70°C); Rel. Humidity: 5%-95% RH (non-condensing).
- Dimension(W*H*D): 0.98in*3.94in*3.54in (25mm*100mm*90mm).
- Mounting: DIN Rail Mounting (35mm).
- Protection Level: IP20
Modbus/EtherNet IP Gateway (GT200-EI-2RS485)
SST Automation’s GT200-EI-2RS485 seamlessly connects multiple Modbus slave devices to the EtherNet IP network.
- EtherNet/IP network is independent with two Modbus networks.
- Ethernet 10/100M adaptive.
- Supports IP addresses conflict detection function.
- Supports the ODVA Standard EtherNet/IP communication protocol.
- Two serial RS-485 interfaces, half-duplex, and baud rate support: 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200; parity support: none, odd, even, mark, space; 1 or 2 stop
- bits.
- GT200-EI-2RS485 acts as master at the side of Modbus network
- Supports 01H, 02H, 03H, 04H, 05H, 06H, 0FH, 10H function codes, can be configured up to 48 Modbus commands for each RS-485 interface;
- Modbus function codes 03H, 04H, 06H and 10H support the “Byte Swap” function, and it can help users solve the problem of data format between two different networks.
- The maximum number of input and output bytes of EtherNet/IP:
- Maximum number of input bytes: 492Bytes.
- Maximum number of output bytes: 492Bytes.
- Power supply: 24VDC (11V ~ 30V), 90mA (24VDC).
- Working temperature:-4°F to 140°F (-20°C to 60°C); Rel. Humidity 5%-95% (non condensing).
- External dimensions (W*H*D): 1.57 in*4.92 in*4.33 in (40mm*125mm*110mm).
- Installation: 35mm DIN rail.
Modbus TCP/EtherNet IP Gateway (GT200-MT-EI)
SST Automation’s GT200-MT-EI can connect Modbus TCP devices to the Ethernet network. It can finish the data exchange between Modbus TCP network and EtherNet/IP network.
- Acts as slave at the side of EtherNet/IP, support ODVA standard EtherNet/IP communication protocol.
- Ethernet 10/100M self-adaptive;
- One Ethernet interface; Modbus TCP and EtherNet/IP share this interface together.
- EtherNet IP Max input bytes: 492 bytes, max output bytes: 492 bytes.
- As Modbus TCP master:
- Supports visiting at most 36 different IP or Modbus TCP slaves of different unit ID, support function code 01H, 02H,03H, 04H, 05H, 06H, 0FH, 10H.
- Acts as slave at the Modbus TCP side, supports 36 TCP connections, supports function code 03H, 04H, 06H, 10H.
- Provides byte swap function: No swap, double-byte swap, four-byte swap.
- Power Supply: 9V~30VDC.
- Operating Temp.: -4°F to 140°F (-20ºC to 60ºC); Rel. Humidity: 5% ~ 95% (non-condensing).
- Dimension (W*H*D): 1.57in*4.92in*4.33in (40mm*125mm*110mm).
- Mounting: DIN Rail Mounting (35mm).
- Protection class: IP20.
Modbus/IEC61850 Gateway (iGate-850)
SST Automation’s iGate-850 provides a seamless information flow between Modbus and IEC61850 networks; iGate-850 can connect multiple devices with RS-232/RS422/RS-485 interface to IEC61850 network.
- One way 10/100 BASE-T self-adaptive Ethernet, RJ45 interface
- Supports IEC 61850-8-1 (MMS) and GOOSE (meeting the mechanism of fast message of substation automation system)
- Two ends of the network support debugging functions
- Maximum data points:800; supports up to 2 IEC61850 client stations and up to 20 Modbus slave numbers
- Transmission mode supports Modbus RTU and ASCII; The serial baud rate supports 200~38400bps
- Free configuration software and ICD modeling software provided
- Low power consumption: 3W@24VDC, no fan.
- Through IEC61850-10KEMA certification
- Operating Temp: -40°F to 158°F(-40ºC to 70ºC); Humidity: 5%~ 95% (non-condensing).
- Dimension (W*H*D): 1.57in*4.92in*4.33in (40mm*125mm*110mm).
- Mounting: DIN Rail Mounting (35mm)
Modbus/Thingworx Gateway (IOT600-TWS-TS)
SST Automation’s IOT600-TWS-TS Gateway allows ThingWorx users to connect Modbus RTU slaves or Modbus TCP devices with easy configuration. The IOT600-TWS-TS can be used as edge gateways that securely connect industrial Modbus equipment over Ethernet networks to ThingWorx
- Two independent RS485 interfaces, baud rate: 9600~115200bps, 1KV galvanic isolated.
- Modbus RTU command has auto demotion and error handling functions.
- Mapping Modbus data to properties of one thing easily.
- Supports TLS/SSL.
- Power supply: 24VDC (9V-30V), 90mA (24VDC), Redundant power supply.
- Operating Temp.: -4°F to 140°F (-20°C to 60°C); Rel. Humidity: 5%-95% (non-condensing).
- Dimension (W*H*D): 1.57 in*4.92 in*4.33 in (40mm*125mm*110mm).
- Mounting: DIN Rail Mounting (35mm)
Empower Your Industrial Connectivity with SST Automation Gateways
Experience the power of seamless data exchange and enhanced communication with SST Automation gateways.